How to size a portable power station: Wh, W and surge, with worked maths
Affiliate links. Disclosure
Checked: 2026-10-25.
A power station has three numbers that matter for sizing: capacity in watt-hours (Wh), continuous AC output in watts (W) and surge (peak) output in W. Get all three right and the unit will start your loads and run them long enough.
The three numbers
- Capacity (Wh) is the energy stored. It decides how long things run.
- Continuous output (W) is the most power the inverter can deliver steadily. It decides what can run at the same time.
- Surge output (W) is a short peak for motor start-up (fridges, pumps, compressors). It decides whether a motor starts.
Pinned example models (from manufacturer pages, checked 2026-10-25):
| Model | Capacity | Continuous AC | Surge / peak | Source |
|---|---|---|---|---|
| EcoFlow DELTA 3 Plus | 1024 Wh | 1800 W (2200 W with X-Boost) | 3600 W | https://us.ecoflow.com/products/delta-3-plus-portable-power-station |
| Jackery Explorer 1000 v2 | 1070 Wh | 1500 W | 3000 W | https://www.jackery.com/products/jackery-explorer-1000-v2 |
| Anker SOLIX C1000 | 1056 Wh | 1800 W | 2400 W ("AC Surge Output"; delivered via SurgePad, see Step 5) | https://www.ankersolix.com/products/c1000 |
Step 1: list your loads
Read the watts from each appliance's label or manual. The numbers below are made-up examples to show the maths, not measurements; replace them with your own.
| Example load | Running W (example) | Hours per day (example) | Wh per day |
|---|---|---|---|
| Wi-Fi router | 12 | 24 | 288 |
| Laptop | 60 | 5 | 300 |
| LED lamp | 10 | 6 | 60 |
| Total | 82 W at once | 648 Wh |
Step 2: allow for conversion losses
A power station's AC inverter is not 100% efficient, so you get less than the rated Wh at the outlet. None of the three manufacturers publishes an AC inverter efficiency figure on the spec pages, user guides or FAQ pages we checked (2026-10-25). For planning, this guide uses an assumed 85%; treat it as our assumption, not a manufacturer spec.
Usable Wh ≈ rated Wh × 0.85
- DELTA 3 Plus: 1024 × 0.85 ≈ 870 Wh
- Explorer 1000 v2: 1070 × 0.85 ≈ 910 Wh
- SOLIX C1000: 1056 × 0.85 ≈ 898 Wh
Step 3: runtime
Runtime (hours) ≈ usable Wh ÷ load W
For the 82 W example load on a DELTA 3 Plus: 870 ÷ 82 ≈ 10.6 hours. The daily 648 Wh fits in about 870 Wh with roughly 220 Wh spare.
Worked check for a single 100 W load on each pinned unit:
- DELTA 3 Plus: 870 ÷ 100 ≈ 8.7 h
- Explorer 1000 v2: 910 ÷ 100 ≈ 9.1 h
- SOLIX C1000: 898 ÷ 100 ≈ 9.0 h
Step 4: check continuous watts
Add up everything that might run at the same moment. That total must stay below the continuous AC rating. An example 1500 W kettle plus an example 300 W load (1800 W together) would exceed the Explorer 1000 v2's 1500 W rating but sit at the DELTA 3 Plus and SOLIX C1000's 1800 W limit, which leaves no headroom. We found no manufacturer figure for how much headroom to leave, so this guide does not recommend a specific margin.
Step 5: check surge
Motors can draw several times their running watts for a moment at start-up. The appliance manual or label sometimes lists a starting or locked-rotor figure; if it does not, ask the appliance manufacturer. This guide does not use a generic start-up multiplier because we found no official one. The starting watts must stay below the station's surge figure.
Note on "boost" modes: EcoFlow X-Boost and Anker SurgePad let resistive loads above the rated output run at reduced power. Anker's C1000/C1000X user guide (model A1761) says SurgePad lets the unit "power high-wattage devices up to 2400W without overload", turns on when total output exceeds the rated output, does not work in bypass mode, and "does not support precision instruments and other devices that have voltage protection or strict voltage requirements". So Anker's 2400 W figure is a SurgePad limit for heat-type loads, not a motor-start surge rating; Anker does not publish a separate motor-start surge figure on the pages we checked. C1000 and C1000X share one user guide and model number (A1761).
Quick sizing worksheet
- Total running W of things used together = ____ W (must be below continuous rating)
- Largest starting W of any motor = ____ W (must be below surge)
- Daily Wh = sum of (W × hours) = ____ Wh
- Needed rated Wh ≈ daily Wh ÷ 0.85 (assumption) = ____ Wh
Affiliate placeholder: EcoFlow / Jackery / Anker SOLIX via Impact (no program active, no link)
Sources
- EcoFlow DELTA 3 Plus product and spec page: https://us.ecoflow.com/products/delta-3-plus-portable-power-station (checked 2026-10-25)
- Jackery Explorer 1000 v2 product and tech specs: https://www.jackery.com/products/jackery-explorer-1000-v2 (checked 2026-10-25)
- Anker SOLIX C1000 product, tech specs and FAQ: https://www.ankersolix.com/products/c1000 (checked 2026-10-25)
- Anker SOLIX C1000/C1000X user guide (A1761): https://service.ankersolix.com/article-description/Anker-SOLIX-C1000-C1000X-Portable-Power-Station-USER-GUIDE-A1761-en-GB (checked 2026-10-25)
Fact-check list
- ☑ Capacities 1024 / 1070 / 1056 Wh match the three spec pages (2026-10-25)
- ☑ Continuous 1800 / 1500 / 1800 W and surge 3600 / 3000 W match EcoFlow and Jackery pages
- ☑ Anker C1000 surge: user guide (A1761) confirms 2400 W is the SurgePad limit; C1000 and C1000X share model A1761 (checked 2026-10-25)
- ☐ Anker separate motor-start surge figure: not published on pages checked; guide makes no claim
- ☐ Inverter efficiency: not published by EcoFlow, Jackery or Anker on pages/manuals checked; 85% kept as a labelled assumption
- ☐ Headroom margin and motor start-up multiplier: no official source found; guide makes no claim
- ☑ Example loads are labelled as examples, not measurements
- ☑ Arithmetic re-checked: 1024×0.85=870.4; 870/82=10.6; 870/100=8.7